CDU32700 L2L 2700kW

CDU32700 L2L 2700kW

The 2700kW CDU is a liquid-to-liquid (L2L) Coolant Distribution Unit. It features dual plate heat exchangers for efficient heat transfer. Heat is transferred from the secondary-side coolant loop to the primary-side chilled water loop, delivering reliable cooling performance.

Key Features

Key FeatureDetails
Pump Redundancy• The CDU features a 2+1 redundant circulating pump configuration with cyclic switchover. The system remains operational even if one pump fails.
Easy Maintenance• The pumps feature a modular skid-mounted design for easy maintenance and replacement.
• The filters feature a hot-swappable design, enabling tool-free maintenance without system shutdown.
High Cooling Capacity in a Compact Footprint• A highly integrated piping layout reduces the footprint to just 1200×1200 mm (L×W).
• The CDU delivers up to 2700 kW of cooling capacity at ATD = 4.
• A single CDU supports cooling for up to 12 NVIDIA Vera Rubin NVL72 systems (220 kW each) or 18 NVIDIA GB300 systems (150 kW each).
Flexible Movement and Handling• The CDU is equipped with integrated forklift slots at the base for easy handling and transportation. The base structure also enables flexible on-site positioning, simplifying installation and deployment.
Technical Specifications

CDU32700 L2L 2700kW Specifications

Complete technical data for Gerchamp Bluearth 2700 kW / 54U Liquid-to-Liquid In-Row CDU

ParameterSpecs
GENERAL-
Solution typeL/L CDU
Cooling capacity2700 kW @ approach temperature 4°C
Primary flow rate: 3025 LPM
Secondary flow rate: 3480 LPM
Dimensions1200(W) × 1200(D) × 2400(H) mm
Secondary liquidPropylene glycol 25 wt%
Noise<85 dB
PumpN+1
Liquid volumeCDU: 80 L
Operating temperaturePG25: 38°C/49.5°C
WeightRadiator: 950 kg
Floor loading, wetAssembly: 1100 kg
POWER SUPPLY-
Power consumption20 kW
Power input1P 380–480 VAC, 50/60 Hz
Connector: IEC 60320-C20
Power redundancy2N+1
mPUE-
mPUE1.10
PRIMARY SIDE-
Primary-side piping connectionsDN150
Primary-side flow rate209 m³/h
SECONDARY SIDE-
Secondary-side piping connectionsDN150
Secondary-side flow rate181 m³/h
Secondary-side design pressure<2 bar
SYSTEM INTERFACE-
System interface1× RJ45 Ethernet
4× M12 for external leak/liquid level
COMMUNICATION INTERFACE-
Communication platformHMI, SNMP, Modbus
MONITORING-
Monitoring• 4× temperature: secondary inlet/outlet and ambient/dew point
• 4× pressure: secondary inlet/outlet
• 2× flow rate: secondary
• 2× leak detection: internal/external
• 2× liquid level: external
• Power meter
Swipe horizontally to view all specifications.