CDU4175 L2A 175kW
CDU4175 L2A 175kW
The 175 kW / 48U L2A Sidecar CDU is a liquid-to-air (L2A) cooling solution capable of meeting the cooling requirements of the NVIDIA Vera Rubin NVL72 platform.
It delivers up to 175 kW of cooling capacity at ATD = 10, making it ideal for high-density AI and HPC applications.
Its unique L2A architecture provides high cooling capacity without requiring changes to existing data center infrastructure. This enables hybrid liquid cooling deployment in conventional air-cooled data centers.
With infrastructure-free installation and rapid deployment, it provides an efficient solution for data centers transitioning from air cooling to liquid cooling.
Features
| Key Feature | Details |
|---|---|
| Ultra-High Deployment Density | • Optimized for the ideal balance between compact dimensions and cooling performance. • Delivers up to 175 kW of cooling capacity at ATD = 10, or 125 kW at ATD = 5, within a width of only 900 mm. |
| Intelligent Monitoring | • The CDU comes standard with an intelligent control system. • It supports local and remote system parameter configuration, operating status monitoring, runtime recording, and alarm information inquiry. System parameters and fault data are automatically stored and retained after power loss. |
| Hot-Swappable Design | • The pumps and filters feature a hot-swappable design. • Tool-free maintenance can be performed on site without system shutdown. |
| Pump Redundancy | • Each CDU is equipped with two pumps, supporting cyclic operation and automatic switchover in case of failure. |
| Intelligent Control | • Supports both Constant Flow and Constant Pressure operating modes. • Allows flexible system configuration to meet different deployment requirements. |
| Modular Design | • Supports both standalone and parallel operation. • A single CDU supports a fully loaded NVIDIA GB300 NVL72 system. • Two CDUs operating in parallel can support the cooling requirements of NVIDIA Vera Rubin NVL72, including the next-generation Ultra version. |
CDU4175 L2A 175kW Specifications
Complete technical data for Gerchamp Bluearth 175 kW / 52U Liquid-to-Air Sidecar CDU
| Parameter | Specs |
|---|---|
| GENERAL | - |
| Solution type | L/A air cooled |
| Cooling capacity | 175 kW @ approach temperature 10°C Primary flow rate: 22,000 CFM Secondary flow rate: 175 LPM |
| Dimensions | Assembly: 900(W) × 1300(D) × 2300(H) mm |
| Secondary liquid | Propylene glycol 25 wt% |
| Noise | <85 dB |
| Pump | 1+1 |
| Liquid volume | Assembly: 38 L CDU: 10 L Tank: 28 L |
| Operating temperature | Ambient: 35°C PG25: 45°C/60°C |
| Weight | Assembly: 485/501 kg RPU: 95/100 kg Radiator: 120/135 kg |
| Floor loading, wet | Assembly: 625 kg |
| POWER SUPPLY | - |
| Power consumption | 12.5 kW |
| Power input | 3P 380–415 VAC, 50/60 Hz |
| Power redundancy | N+1 |
| mPUE | - |
| mPUE | 1.10 |
| PRIMARY SIDE | - |
| Primary-side piping connections | 2-inch hose barb fitting |
| Primary-side flow rate | <22,000 CFM |
| SECONDARY SIDE | - |
| Secondary-side piping connections | 2-inch sanitary clamp |
| Secondary-side flow rate | <175 LPM |
| Secondary-side design pressure | <2 bar |
| SYSTEM INFERFACE | - |
| System interface | 1× RJ45 Ethernet 4× M12 for external leak/liquid level |
| COMMUNICATION PLATFORM | - |
| Communication platform | HMI, SNMP, Modbus |
| MONITORING | - |
| Monitoring | • 4× temperature: secondary inlet/outlet and ambient/dew point • 4× pressure: secondary inlet/outlet • 1× flow rate: secondary • 5× leak detection: internal/external • 2× liquid level: external • Power meter |