CDU4175 L2A 175kW

CDU4175 L2A 175kW

The 175 kW / 48U L2A Sidecar CDU is a liquid-to-air (L2A) cooling solution capable of meeting the cooling requirements of the NVIDIA Vera Rubin NVL72 platform.

It delivers up to 175 kW of cooling capacity at ATD = 10, making it ideal for high-density AI and HPC applications.

Its unique L2A architecture provides high cooling capacity without requiring changes to existing data center infrastructure. This enables hybrid liquid cooling deployment in conventional air-cooled data centers.

With infrastructure-free installation and rapid deployment, it provides an efficient solution for data centers transitioning from air cooling to liquid cooling.

Features

Key FeatureDetails
Ultra-High Deployment Density• Optimized for the ideal balance between compact dimensions and cooling performance.
• Delivers up to 175 kW of cooling capacity at ATD = 10, or 125 kW at ATD = 5, within a width of only 900 mm.
Intelligent Monitoring• The CDU comes standard with an intelligent control system.
• It supports local and remote system parameter configuration, operating status monitoring, runtime recording, and alarm information inquiry. System parameters and fault data are automatically stored and retained after power loss.
Hot-Swappable Design• The pumps and filters feature a hot-swappable design.
• Tool-free maintenance can be performed on site without system shutdown.
Pump Redundancy• Each CDU is equipped with two pumps, supporting cyclic operation and automatic switchover in case of failure.
Intelligent Control• Supports both Constant Flow and Constant Pressure operating modes.
• Allows flexible system configuration to meet different deployment requirements.
Modular Design• Supports both standalone and parallel operation.
• A single CDU supports a fully loaded NVIDIA GB300 NVL72 system.
• Two CDUs operating in parallel can support the cooling requirements of NVIDIA Vera Rubin NVL72, including the next-generation Ultra version.
Technical Specifications

CDU4175 L2A 175kW Specifications

Complete technical data for Gerchamp Bluearth 175 kW / 52U Liquid-to-Air Sidecar CDU

ParameterSpecs
GENERAL-
Solution typeL/A air cooled
Cooling capacity175 kW @ approach temperature 10°C
Primary flow rate: 22,000 CFM
Secondary flow rate: 175 LPM
DimensionsAssembly: 900(W) × 1300(D) × 2300(H) mm
Secondary liquidPropylene glycol 25 wt%
Noise<85 dB
Pump1+1
Liquid volumeAssembly: 38 L
CDU: 10 L
Tank: 28 L
Operating temperatureAmbient: 35°C
PG25: 45°C/60°C
WeightAssembly: 485/501 kg
RPU: 95/100 kg
Radiator: 120/135 kg
Floor loading, wetAssembly: 625 kg
POWER SUPPLY-
Power consumption12.5 kW
Power input3P 380–415 VAC, 50/60 Hz
Power redundancyN+1
mPUE-
mPUE1.10
PRIMARY SIDE-
Primary-side piping connections2-inch hose barb fitting
Primary-side flow rate<22,000 CFM
SECONDARY SIDE-
Secondary-side piping connections2-inch sanitary clamp
Secondary-side flow rate<175 LPM
Secondary-side design pressure<2 bar
SYSTEM INFERFACE-
System interface1× RJ45 Ethernet
4× M12 for external leak/liquid level
COMMUNICATION PLATFORM-
Communication platformHMI, SNMP, Modbus
MONITORING-
Monitoring• 4× temperature: secondary inlet/outlet and ambient/dew point
• 4× pressure: secondary inlet/outlet
• 1× flow rate: secondary
• 5× leak detection: internal/external
• 2× liquid level: external
• Power meter
Swipe horizontally to view all specifications.

Get in Touch

Have a question or want to learn more? Send us a message.