GZC-9038S

GZC-9038S

Gerchamp’s GZC-9038S Nickel-Zinc Battery Cabinet integrates a self-developed intelligent battery management system (BMS) with Gerchamp’s 8XNFG90 nickel-zinc battery - 10C high-rate discharge, intrinsically safe, zerothermal runaway risk.

An ideal replacement for traditional lead-acid battery cabinet and racks, it fits critical power scenarios including data centers, computing rooms, industrial backup, rail transit, and telecom base stations.

Features

Technical ParameterValue / Details
Intrinsic SafetyAqueous electrolyte with no thermal runaway, fire, or explosion risk; no open circuit during discharge, ensuring reliable series-connected battery strings.
10C Discharge RateSupports 0.5C–10C discharge, balancing capacity and power to suit different applications.
Wide Temperature RangeStable, efficient performance from −20°C to 55°C, breaking traditional battery temperature limits.
Rapid DeploymentCompatible with mainstream MW-class UPS inverters, directly replacing existing lead-acid battery cabinets with no power distribution system modifications.
Eco-Friendly>90% recyclable and made from non-polluting materials, supporting clean energy and cutting carbon footprint.
Smaller and LighterHigher power density with 1/2 size reduction and 2/3 weight reduction of lead-acid batteries at same capacity.
Technical Parameters

Product Specifications

Specifications of Gerchamp new-generation GZC-9038S Nickel-Zinc Battery Cabinet.

ModelGZC-9038SGZC-9037SGZC-9036S
Battery configuration38S37S36S
Cabinet energy45kWh44kWh43kWh
Rated voltage501VDC488VDC475VDC
Charging voltageFloat charge 562.4VDC, equalization charge 577.6VDCFloat charge 547.6VDC, equalization charge 562.4VDCFloat charge 532.8VDC, equalization charge 547.2VDC
ItemSpecification
Cell nominal capacity90Ah (discharge at 90A to 10.4V, 25℃)
Cell nominal energy1.188kWh
Battery optionNickel-zinc battery - 8XNFG90
Charging current27A~90A
Standard charging current45A
Maximum discharge current900A
Charging time3-5 hours
ApplicationUsed for backup power scenarios of less than 15 minutes
System BMS Function
MonitoringMonitor and analysis battery voltage, internal resistance, temperature, charge/discharge current, equalization voltage, float voltage, etc.
State estimationSOC, SOH
Self-testAutomatic test cycle can be set without manual intervention
AlarmSupport alarm management; when any value exceeds the limit, an alarm is automatically triggered, local indicator lights up, buzzer sounds, alarm register is set, and dry contact is activated
Data recordSupport historical data recording / event alarm recording
Data communication1 Ethernet port output
Communication protocols: MODBUS/RTU, MODBUS/TCP, SNMP
Built-in WEBSupport WEB remote real-time data viewing, function control, and parameter configuration
Safety
CertificationUL 9540A, EU2023-1542, RoHS, UL 94 V-0
Circuit breaker protectionIn case of overload fault, the circuit breaker trips
Fuse protectionIn case of short circuit fault, the fuse blows
Operating temperature rangeDischarge: -20℃~+55℃ Charge: 0℃~+40℃
Storage temperature range-20℃~+55℃
Storage periodAfter storage exceeding 3 months at 25℃, the battery requires recharging
Humidity range0~85%, non-condensing
Cooling methodAir cooling
Mechanical
Dimension530(W) x 1000(D) x 2100(H) mm
Weight1100kg