GHV3S 3S Module for BESS
GHV3S
GHV3S integrates BMS (battery management system), PCS (power conversion system), EMS (energy management system) and HV Box (high-voltage box) in one module. The self-developed design can deliver intelligent product synergy, improve safety performance, save on hardware costs, increase conversion efficiency, shorten the development cycle and reduce the difficulty of operation and maintenance.
Key Features
| Technical Parameter | Value / Details |
|---|---|
| Low Cost | All-in-one design reduces size and cuts total development costs. |
| High Efficiency & Stability | 3S strategic integration ensures fast response and high stability. |
| Flexible Configuration | Flexible configuration adapts to diverse scenarios and ESS products. |
| Convenient O&M | Self-developed system with smart collaboration simplifies O&M. |
Technical Parameters
Product Specifications
Complete technical data for the GHV3S 3S Module.
| Parameter | Result |
|---|---|
| Description | GHV3S-P100U10F / GHV3S-P135U10F |
| Rated power supply | 220Vac / 100~240Vac |
| Power consumption | <200W (without load) |
| Maximum conversion efficiency | 98% |
| Dimensions (LWH) / weight | 794800235mm/<82.55kg / 7941000235mm/<100kg |
| Cooling method | Air cooling |
| Noise level | <75dB |
| Protection rating | IP20 |
| Operating temperature / storage temperature / relative humidity | -20~+50℃/-40~+125℃/0~95% (non-condensing) |
| Altitude | <3000m |
| Rated AC power | 100kW / 135kW |
| Wiring | 3-phase 3-wire (on-grid mode), 3-phase 3-wire/3-phase 4-wire (off-grid mode) |
| AC overload capacity | 10% overload |
| Permissible voltage | 380/400Vac(-15%~15%) / 400Vac(-10%~15%) |
| Permissible frequency | 50Hz(-2.5~2.5) / 50Hz(-0.5~0.5) |
| Total harmonic current distortion | ≤5% |
| Power factor | 0.99(-1~1) / (-1~1) |
| Rated DC power | 100kW / 135kW |
| Maximum DC current | 169A / 228A |
| DC access channel | 650~900V / 650~950V |
| / | 2-channel LAN, 3-channel CAN (2-channel CAN 2.0, 1-channel CAN FD), 4-channel RS485, 1-channel RS232, 2-channel fibre signal |
| 4-channel DO*L | Voltage range: 9~32Vdc |
| Output port | Current: 2.2A/single-channel maximum and 1.1A continuously |
| Single-channel DO*L rated power: 26.4W | Single-channel DOL rated power: 26.4W Dual-channel DOL total rated power: 52.8W Four-channel DO*L total rated power: 105.6W |
| Single-channel instantaneous power: 192W | Single-channel DOL instantaneous power: 192W Dual-channel DOL instantaneous power: 384W Four-channel DO*L instantaneous power: 768W |
| 4-channel dry contact output | Voltage: 24Vdc/1A Electrical isolation: 3000Vdc |
| 7-channel DI*L and 2-channel passive DI | Low voltage range: <0.5VDC |
| Storage / internal memory / port | 8GB/2GB/1-channel USB port (USB2.0) |
Scroll to view all parameters