150kW 4U In-Rack CDU Liquid Cooling
150kW/4U
The 150 kW 4U CDU is a compact liquid-cooling core unit installed in a standard 19-inch server rack, with a height of 4U. The 4U CDU is an optimal solution for addressing the heat dissipation bottleneck in high heat-density computing, such as AI large models and high-performance computing (HPC). Within an extremely compact 4U space, it provides high cooling capacity, with high density, high efficiency, high reliability and ease of deployment, serving as key infrastructure for the transition from air cooling to liquid cooling in data centres.
Key Features
| Technical Parameter | Value / Details |
|---|---|
| Pump Redundancy & Monitoring and Control | Equipped with two pumps, supporting cyclic operation and automatic switchover in the event of failure. Supports local and remote system parameter configuration, operating status monitoring, runtime recording and alarm information enquiry. System parameters and fault data are automatically stored and retained after power loss. |
| Rack-Mount Design | Standard 4U rack-mounted design enables easy installation and reduces retrofit complexity in existing data centres. The dual-pump configuration allows convenient maintenance and replacement, improving overall system reliability. |
Technical Parameters
Product Specifications
Complete technical data for the 150kW/4U L2L in-rack CDU.
| Parameter | Result |
|---|---|
| TECHNICAL PARAMETER: 150KW / 4U / L2L CDU | - |
| Technical parameter | 150kW / 4U / L2L CDU |
| Rated cooling capacity | 152 kW @ 4.0°C ATD |
| Maximum flow rate – single pump operation | 152L/min, external pressure difference 2.0bar |
| Maximum flow rate – dual pump operation for N+ redundancy | 230L/min, external pressure difference 3.4bar |
| Secondary coolant type | Pure water or PG25 |
| Pump redundancy | Single pump (N) / dual pump (N+N) / dual pump switchover |
| Primary pressure drop | 0.8 bar (PG25) under typical conditions (150 L/min) |
| Secondary coolant temperature range | 10–55°C, with dew point control as standard |
| Maximum power consumption | 1.5 kW (single pump) 2.7 kW (dual pump) |
| Dimensions (H × W × D) and weight | 178 mm x 450 mm x 1055 mm, 90 kg |
| Noise level at 3m (10ft) | < 54 dBA |
| Power supply (Europe, Asia and Taiwan) | 220-270 V 50/60 Hz or DC48V |
| Dual power supply (ATS) | Optional feature |
| Primary connections | Rear, 1-inch sanitary flange |
| Secondary connections | Rear, 1-inch sanitary flange |
| Secondary filtration | Optional 50um/20um |
| Communication | RS485 RTU Modbus, TCP/IP SNMP |