500kW Modular AI Data Centre

500kW All-in-One Modular AIDC

The Gerchamp 500 kW All-in-One Modular AI Data Centre integrates battery cabinets, UPS cabinets, the secondary-side heat load, CDU, and a primary-side dry cooler within a 12-metre container. The system combines power supply and liquid cooling in a single containerised solution.

It can be deployed close to renewable energy generation sites or at locations with idle or underutilised power resources. By utilising locally available power and turning it into usable AI computing capacity, the solution enables rapid deployment of large-capacity, high-density mobile data centres for supercomputing clusters.

Advantages

Technical ParameterValue / Details
Prefabricated integration for rapid deploymentBIM-based digital engineering and factory prefabrication integrate server racks, power distribution, cable management, fire protection, and liquid cooling pipework into a factory-tested system, reducing on-site installation and system integration for faster deployment.
Modular scalability and flexible redeploymentStandardised containerised modules support phased deployment and on-demand expansion, while enabling relocation and redeployment as project needs evolve.
Reliable power architectureThe power module integrates Gerchamp-developed UPS, NiZn BBU and BMS, with an ATS included as standard. The system supports grid-connected, off-grid and backup operation for reliable power delivery to IT loads.
Unified monitoring and intelligent operationsThe Gerchamp-developed DCIM platform provides unified monitoring of power, liquid cooling, environmental, and security systems. It supports real-time alerts, PUE analysis, asset lifecycle management, and capacity planning for centralised visibility and management.
Technical Parameters

Product Specifications

Complete technical data for the Gerchamp 500kW All-in-One Modular AI Data Centre.

ParameterResult
GENERAL
Weight13,737 / 17,993 kg (excl. / incl. coolant and servers)
Dimensions12,192 × 2,438 × 2,896~3,496 mm
Noise Level (dBA)54–70 dBA at 10 m (indoor/outdoor)
COOLING SYSTEM
Circulation PumpHigh-Efficiency Coolant Circulation Pump, N+1
Heat Rejection EquipmentDry cooler
Total Heat Rejection CapacityUp to 465,260 kcal/h
Rated Server Operating Temperature45–65 °C @ DB = 37 °C
Primary-Side CoolantEthylene Glycol/Water Mixture (mixing ratio adjusted based on deployment location; approx. 345 L)
THERMAL PERFORMANCE
Rated Design Condition541kW
High-Ambient Design Condition500kW
ELECTRICAL SPECIFICATIONS
Input Power3-Phase, 380–480 V, 60 Hz
Maximum IT Load500 kW
UPS Backup Runtime15 min at Full Load
Auxiliary Power Consumption29.5 kW (PUE = 1.06 at full load)
CONTROLS AND MONITORING
PLCSiemens S70 Series
Touchscreen HMI10“ MCGS (Wi-Fi or 4G available)
CommunicationModbus RTU (RS485) and TCP/IP
AIR CONDITIONING SYSTEM
IT Compartment Air ConditioningOptional: 2 × 35 kW Units, N+1 Redundancy
Power Compartment Air Conditioning12 kW Unit
FIRE PROTECTION
Fire Detection CoverageInside IT Racks, Aisles, and Power Compartment
Fire Detection SystemEarly Warning Detection, Supplemental In-Compartment Detection, and Fire Alarm Control Panel
Fire Suppression SystemHFC-227ea Clean Agent Fire Suppression
Fire Alarm Interlock LogicIT Equipment Power-Off + Automatic Shutdown of CDU / Cooling Pumps
Fire Control and Remote Signalling (Integration with Power and Environmental Monitoring System)Signals to Site Monitoring System: Alarm, Trouble, Supervisory