This page takes a liquid-to-liquid CDU as its example, where a plate exchanger sits between facility water and the rack loop. A liquid-to-air unit uses a coil and a fan, and its airside behaviour has its own treatment elsewhere.
CDU heat transfer in a plate exchanger follows the same thermal principles as any other exchanger, and those principles set what a unit can be rated at.
The parent article covers what the exchanger does in the loop, in its section on CDU internal components and what each one does. This article examines the thermal and hydraulic behaviour of the plate exchanger.
Heat Transfer Driving Force in a Plate Pack
Heat moves from the warmer stream to the colder one. The rate depends on the coefficient, the area and the temperature difference between them, and those three multiply into the duty.
Temperature Difference as the Driver
A larger temperature difference raises the heat-transfer rate for a given surface. The difference also varies along the flow path, and how it varies depends on the arrangement and on each stream’s heat capacity.
At any point along the plates, heat moves from the warmer fluid to the cooler one. The figure for the whole pack is an effective mean difference, usually described by the logarithmic mean, which weighs both ends.
The Plate as the Barrier
One plate separates the two fluids. It carries heat across its thickness and keeps the streams apart, which is why a plate exchanger transfers heat without mixing the circuits.
The plate thickness and its material contribute one resistance. In a clean unit with thin stainless plates this term usually stays small relative to the two fluid films.
Resistances Add in Series
Heat passes a film of secondary fluid, the plate, and a film of primary fluid. Each layer resists the heat flow, and the overall coefficient follows from their sum.
One term can be much larger than the others, and then it shapes the result on its own. That approximation holds for many thin-metal, water-to-water packs. The smaller terms still contribute, and a change in one of them shows up in the total.
A fouled surface adds a layer on either side. That is enough to say here, since fouling has its own treatment elsewhere.
Plate Turbulence Trade-Off
With temperatures and duty set by the loop, a designer works on two things: how much surface the heat crosses, and how much disturbance the fluid sees along it. Each adjustment has a cost that depends on how it is made.
Wavy Plates and Turbulence
Plate surfaces carry a chevron or herringbone pattern. The pattern turns the flow repeatedly and breaks up the film that would otherwise insulate the surface.
A thinner film passes heat more easily, so the same area carries more duty. The pattern also raises the pressure the pump has to produce, and the size of that rise depends on the pattern angle and the flow.
Channel Width and Plate Count
Two adjustments are often written as one. Adding plates in a frame with room to spare raises the area and lengthens the pack along its stacking direction.
Narrowing the channel is a separate design choice. At the same envelope it fits more plates and more parallel passages, and the velocity in each passage follows from the total flow and the flow area those passages present. Plate count, gap and flow rate are therefore evaluated together.
The Cost of Each Adjustment
More surface takes volume and material. More disturbance takes pumping power, and pumping shows up twice, once in electricity and once in the heat the pump adds to the fluid.
The costs do not always move the same way. More parallel channels can lower velocity and pressure drop while raising area. A narrower gap raises the heat-transfer intensity, and its hydraulic effect depends on the passage count and the flow.
Counterflow Arrangement and the Approach
The two streams can move in the same direction or in opposite ones. The choice changes how the temperatures line up along the plates, and how close the two streams can come by the time they leave.
Four Temperature Points
A counterflow pack pairs the warm end of one stream with the cold end of the other. At the end where secondary return enters, the warmed primary water leaves. At the end where secondary supply leaves, cooler facility water enters.
| End of the pack | Secondary side | Primary side |
|---|---|---|
| Warm-secondary end | Inlet: warm return from the racks | Outlet: warmed water back to the facility |
| Cold-secondary end | Outlet: cooled supply to the racks | Inlet: cooler facility water |
Every local pair keeps the primary side colder than the secondary side, so heat moves in one direction throughout.
Counterflow and Temperature Cross
Under comparable inlet temperatures, flow rates and overall heat-transfer conductance, counterflow gives a larger mean difference than parallel flow. A pack built that way carries the same duty in less area, or reaches a smaller approach in the same area.
Counterflow also allows a temperature cross, where the cold stream leaves warmer than the warm stream leaves. The cross describes the two outlets relative to each other. No local pair runs backwards.
The approach a datasheet quotes follows from the arrangement, the area and the flow rates together. It can be asked for at the design stage, and the value a unit reaches in service depends on the conditions it runs at.
CDU Pressure Drop on Primary and Secondary Sides
Higher heat-transfer performance usually costs pressure drop on the secondary side. A change that raises the coefficient usually raises the pressure the pump has to produce, and how much depends on the geometry and the flow regime.
Pressure Drop and Flow Regime
Pressure loss through a channel rises with velocity, and the rate depends on the channel geometry and on whether the flow stays turbulent across the range.
Pressure drop rises nonlinearly with flow in most plate packs. The exact relation depends on the fluid properties, the channel geometry and the flow regime, and a change of plate pattern alters it, which is why the two are selected together.
Pumping Cost Against Heat Transfer
A designer can raise velocity to shrink the pack, or widen the channel to cut pumping. The duty sets how much of each is acceptable.
The selected exchanger has to meet the duty within the allowable pressure drop on both sides. Both conditions have to hold at once.
The primary side carries its own pressure drop, and a pack selected on the secondary figure alone can still exceed what the facility loop can spare.
Where a bypass circuit diverts part of the flow around the exchanger, less coolant crosses the plates. The resulting supply temperature depends on the bypass flow, the exchanger flow and how the two streams mix downstream.
Gerchamp’s CDU32700 L2L 2700kW product is listed with dual plate exchangers. The circuit arrangement behind that configuration comes from the unit documentation.
Frequently Asked Questions
Does a CDU exchanger mix the two fluids? No. A plate separates them, and heat crosses the plate while the circuits stay separate. Mixing counts as a leak.
Does more plate area always raise capacity? No. Capacity follows the coefficient, the area and the mean difference together, so added area rarely lifts it in proportion. More plates also change channel width and velocity, and fouling shifts the balance again.
Can a smaller approach be specified? It can be asked for at the design stage. Reaching it takes area, disturbance or flow, and the value a unit holds in service follows the temperatures and flows it actually runs at.
The Bottom Line
Heat crosses the pack through two films and a plate, and the resistances behind the overall coefficient add in series.
Area, disturbance and flow direction each change what a pack can carry, and the cost of each depends on how the change is made. A quoted approach belongs with its conditions, and the pressure drop on both sides belongs in the same review.