How Do Constant Flow and Constant Pressure CDU Modes Differ?

A GERCHAMP liquid-cooling cabinet in a premium battery energy storage facility, framed beside two clearly differentiated hydraulic control paths representing constant-flow and constant-pressure operation.

The constant flow vs constant pressure CDU choice comes down to which variable the controller holds and which one it lets move.

The section on secondary loop hydraulics and the pressure budget sets out what the pump has to overcome. This page covers how the pump behaves while it does so.

Which modes a unit offers, and what else its controller can do, come from its documentation.

CDU Control Mode and What It Holds

Both modes run the same hardware. A pump set moves coolant, a controller reads a sensor, and a drive adjusts speed. The difference is the signal the controller acts on.

The Variable Each Mode Holds

A constant-flow CDU holds total secondary flow at its setpoint. The controller compares measured flow with the target and moves pump speed until the two agree.

A constant-pressure CDU holds a differential between two pressure taps. The controller compares that difference with a setpoint and adjusts speed on the error.

The Variable Left Free

Flow and differential are linked through the loop, so holding one leaves the other to follow the loop’s resistance.

A constant-flow unit lets differential drift with loop resistance. A constant-pressure unit lets total flow drift with it.

Both variables exist in either mode. The controller drives one directly and the other becomes a consequence.

Pump Speed as the Actuator

Both modes act on pump speed. A variable speed drive changes impeller speed and the pump curve moves with it.

Reducing speed cuts flow and head together, and shaft power falls faster than either. The affinity laws describe that relation at comparable operating points, for a similar impeller geometry and a modest speed change. The actual operating point also follows the system curve and the control setpoint.

A pump also has limits at the low end. Below a minimum speed it may fail to hold head, and below the manufacturer’s minimum flow the impeller may recirculate, overheat or vibrate. A setpoint outside those limits is not achievable in either mode.

CDU Pressure Sensor Location

Differential pressure is a difference between two pressures. A reading therefore has two taps behind it, and the pair chosen changes what the setpoint means.

Two Taps Behind One Reading

A sensor across the CDU supply and return headers reads what the unit produces. Across pump suction and discharge it reads the pump’s own rise. Across a pair of taps at the far end it reads what the distribution leaves for the racks.

The three readings differ by the losses between them. A setpoint quoted without its tap locations does not describe the loop condition at the cold plates.

Flow measurement has a similar question. Where a bypass exists, a meter upstream of the take-off may register total pump flow, while a meter downstream may register only what reaches the distribution circuit.

Local Feedback at the Unit

Local feedback closes the loop at the unit. The setpoint can be calculated to cover distribution losses, so a long run is not excluded.

What it requires is a setpoint derived from the loop, plus a check that each branch receives its share through balancing or pressure-independent control.

Remote Feedback at a Branch

Remote feedback closes the loop at a chosen pair of taps near the load. Its advantage is direct: the controller holds the differential that pair sees.

That choice carries conditions. The taps have to represent the least favoured branch, the signal has to reach the controller, and a plan is needed for what happens if it does not. The least favoured branch can also move as the row configuration changes.

Load Change and Part Load Behaviour

Part load covers two events often written as one. Heat load can fall with the hydraulics untouched, or branch valves can close. A branch that still carries load has no flow path once closed, so the second case applies to branches at or near zero load.

The modes respond differently to each.

Lower Heat Load at Constant Hydraulics

Where the cold plates keep their flow and the heat load falls, the return temperature drops and the flow stays put. A constant-flow unit has nothing to correct.

A constant-pressure unit does not reduce flow on a heat load drop either. Its sensor sees the same differential, since the resistance has not changed, so the operating point stays put.

Neither mode saves pump energy on it.

Branches Closing Against the Pump

Where some branches close, loop resistance rises. A constant-flow unit holds its measured flow setpoint, so it raises speed and the differential across the loop rises with it. Where a bypass carries part of that flow, or the meter sits upstream of the bypass, the response can differ.

A constant-pressure unit holds its setpoint instead. Total flow falls as the branches close, and the differential at the measured pair stays where the setpoint put it.

Limits and Bypass Paths

Each mode reaches a different limit. A constant-flow unit runs into a speed ceiling or a pressure limit. A constant-pressure unit runs into minimum speed or minimum flow.

What happens next depends on the controller and the protection logic. A bypass path, a minimum-flow line, a relief setting, or a trip are separate measures.

Bypass paths belong to the pump and loop requirement. A constant-pressure loop with a low minimum flow can need one as well.

Control Mode Selection for a Project

Mode selection follows the loop and its controls. A CDU holds total flow or one differential, and neither reading describes what an individual cold plate receives.

Decision factorConstant flowConstant differential pressure
Typical applicationA defined total-flow requirementVariable-flow branches with modulating valves
Branch closurePump speed may rise to hold measured flowTotal flow falls while the setpoint holds
Main design concernExcess differential and minimum-flow pathsRemote branch flow and sensor location
Part-load energyFollows setpoint and hydraulic changesMay fall when total flow decreases
VerificationFlow split and pressure limitsBranch flow, minimum differential, pump limits

The Controlled Variable in Practice

The controller acts on a total or on one measured difference. Branch flow follows each branch’s resistance unless something on the branch regulates it.

The first question is whether the branches are balanced, whether they carry pressure-independent control, and whether the total held matches the sum the branches need.

Valves and Loop Structure

Branch valves that modulate or close with demand change the hydraulics, and the modes answer that change differently. Branches that hold flow and let temperature vary leave the hydraulics alone.

The loop structure sets the consequence of each mode. A row of fixed-flow branches behaves differently from a row of modulating valves at the same setting.

Cases to Check

Four checks belong with the mode choice. Whether the least favoured branch still receives its design flow. Whether the differential at any branch stays inside its limit. Whether the loop pressure at each point stays inside the working pressure of the parts there. Whether the protections cover both modes.

Overpressure protection is its own function, and a loop needs it in either mode.

A unit that offers both modes can be switched later, within the manufacturer’s approved control procedure and after sensor configuration, setpoints and balancing are rechecked. Gerchamp’s CDU4175 L2A 175kW product lists constant flow and constant pressure as its two operating modes. Its documentation carries the details of feedback, limits and protections.

Frequently Asked Questions

Does constant pressure guarantee flow at every cabinet?

No. It holds one differential between two taps, and branch flow follows each branch’s resistance. Branches need balancing or pressure-independent control to reach design flow, and a pressure-independent valve needs its own differential range to work.

Which mode saves energy at part load?

Neither, on a heat load drop with the hydraulics and setpoints unchanged. Speed can fall when a setpoint is reset or when branch valves close and total flow drops, so the saving depends on the pump curve, the system resistance and the control strategy.

Does constant flow need a bypass?

Not by itself. A bypass or minimum-flow path is needed when the pump or loop cannot tolerate the flow the mode would otherwise hold, and a constant-pressure loop can face the same requirement.

The Bottom Line

Constant flow holds total flow, constant pressure holds one differential, and both act through pump speed while the other variable follows the loop’s resistance.

What reaches a cold plate depends on the branches as much as on the mode. Branch balancing, the branch valves, and a separate overpressure function decide whether the loop stays inside its limits.