title: "CDU3150 L2L 150kW"
description: "Gerchamp Bluearth 150kW L2L CDU is a compact liquid cooling core unit installed in a standard 19-inch server rack, with a height of 4U. The 4U CDU is an optimal solution for addressing the heat dissipation bottlene"
---

# CDU3150 L2L 150kW

Home

Products

CDU3150 L2L 150kW

![Product image](https://www.gerchamp.com/media/page-assets/uploads/2026/05/f77ffff2-62ca-4297-b1c8-a06bee1f8b48.webp)

CDU3150 L2L 150kW

The CDU3150 L2L 150kW is a compact liquid cooling core unit installed in a standard 19-inch server rack, with a height of 4U. The 4U CDU is an optimal solution for addressing the heat dissipation bottleneck of high heat density computing such as Al largemodels and high-performance computing (HPC). Within an extremely compact 4U space, it provides high cooling capacity, featuring high density, high efficiency, high reliability, and ease of deployment, and serves as a key infrastructure for the transition from air cooling to liquid cooling in data centers.

Key Features

| Technical Parameter | Value / Details |
| --- | --- |
| Pump Redundancy & Monitoring And Control | Equipped with two pumps, supporting cyclic operation and automatic switchover in case of failure. Supports local and remote system parameter configuration, operating status monitoring, runtime recording, and alarm information inquiry. System parameters and fault data are automatically stored and retained after power loss. |
| Rack-Mount Design | Standard 4U rack-mounted design enables easy installation and reduces retrofit complexity in existing data centers. Dual-pump configuration allows convenient maintenance and replacement, improving overall system reliability. |

Technical Parameters

Product Specifications

Complete technical data for the 150kW/4U L2L In-Rack CDU.

| Parameter | Result |
|---|---|
| **TECHNICAL PARAMETER: 150KW / 4U / L2L CDU** | - |
| Technical parameter | 150kW / 4U / L2L CDU |
| Rated cooling capacity | 152 kW @ 4.0°C ATD |
| Maximum flow rate – single pump operation | 152L/min, external pressure difference 2.0bar |
| Maximum flow rate – dual pump operation for N+ redundancy | 230L/min, external pressure difference 3.4bar |
| Secondary coolant Type | Pure water or PG25 |
| Pump redundancy | Single pump (N) / dual pump (N+N) / dual pump switchover |
| Primary pressure drop | 0.8 bar (PG25) under typical conditions (150 L/min) |
| Secondary coolant temperature range | 10–55°C, with dew point control standard |
| Maximum power consumption | 1.5 kW (Single pump) 2.7 kW (Dual pump) |
| Dimensions (H × W × D) and weight | 178 mm x 450 mm x 1055 mm, 90 kg |
| Noise level at 3m (10ft) | < 54 dBA |
| Power supply (Europe, Asia and Taiwan) | 220-270 V 50/60 Hz or DC48V |
| Dual power supply (ATS) | Optional features |
| Primary connections | Rear, 1-inch sanitary flange |
| Secondary connections | Rear, 1-inch sanitary flange |
| Secondary filtration | Optional 50um/20um |
| Communication | RS485 RTU modbus, TCP/IP SNMP |

Scroll to view all parameters

### Related Content

#### Related Solutions

- [Finance & Banking](https://www.gerchamp.com/en-US/solutions/battery-management-system-solutions-in-public-utilities) ([Agent MD](https://www.gerchamp.com/en-US/solutions/battery-management-system-solutions-in-public-utilities/raw.md)) - In the financial sector, the stability of power supply for core infrastructure is a non-negotiable baseline.
- [Data Center](https://www.gerchamp.com/en-US/solutions/ups-battery-management-system) ([Agent MD](https://www.gerchamp.com/en-US/solutions/ups-battery-management-system/raw.md)) - Modern data centers handle massive volumes of enterprise and personal data for storage.
- [Liquid Cooling Solutions](https://www.gerchamp.com/en-US/solutions/liquid-cooling-solutions-for-data-centers) ([Agent MD](https://www.gerchamp.com/en-US/solutions/liquid-cooling-solutions-for-data-centers/raw.md)) - Discover liquid cooling infrastructure including Coolant Distribution Units (CDU) and Direct Liquid Cooling Cabinets (DLCC) for AI, HPC and high-density data centers. Improve thermal efficiency, scalability and reliable cooling performance.

#### Related Documents & Downloads

- [CDU3150 L2L 150kW](/media/library/2026/07/acbb4254-0903-4aee-b100-d2c0c0c44290.pdf) - Gerchamp Bluearth Liquid Cooling Series, Liquid-to-Liquid CDU, In-rack, 150kW, Compact 4U size


Related Contents

---

**Navigation**

[Home](https://www.gerchamp.com/en-US/) ([MD](https://www.gerchamp.com/en-US/raw.md)) | [Products](https://www.gerchamp.com/en-US/products/) ([MD](https://www.gerchamp.com/en-US/products/raw.md)) | [Solutions](https://www.gerchamp.com/en-US/solutions/) ([MD](https://www.gerchamp.com/en-US/solutions/raw.md)) | [Blog](https://www.gerchamp.com/en-US/blog/) ([MD](https://www.gerchamp.com/en-US/blog/raw.md)) | [About](https://www.gerchamp.com/en-US/about/) ([MD](https://www.gerchamp.com/en-US/about/raw.md)) | [Downloads](https://www.gerchamp.com/en-US/downloads/) ([MD](https://www.gerchamp.com/en-US/downloads/raw.md)) | [Contact](https://www.gerchamp.com/en-US/contact/) ([MD](https://www.gerchamp.com/en-US/contact/raw.md))