680kW/48U
680kW/48U
The 680 kW CDU is a liquid cooling unit that removes heat generated by equipment through the secondary-side heat exchange via a plate heat exchanger, and transfers the heat away through the primary-side chilled water loop.
Key Features
| Technical Parameter | Value / Details |
|---|---|
| Pump Redundancy | Adopts an N+1 pump configuration with cyclic switchover, ensuring continuous operation in case of single pump failure. |
| High Cooling Capacity In a Compact Footprint | Features a highly integrated piping design, with a footprintof only 1200 x 600 mm (LxW), and is capable of removing up to 680 kW of heat. |
| Easy Maintenance Access | The electrical control cabinet adopts a tiltable structure. During maintenance, such as removing filter elements orreplacing pumps, the cabinet can be lifted via hydraulic supports, providing sufficient operating space. |
| Flexible Movement and Handling | Equipped with four heavy-duty casters at the base. The bottom structure allows for forklift handling for easy loading, and also enables flexible movement on the floor for convenient repositioning. |
Technical Parameters
Product Specifications
Complete technical data for the 680kW/48U L2L In-Row CDU.
| Parameter | Result |
|---|---|
| TECHNICAL PARAMETERS: 680KW / 48U / L2L CDU | - |
| Technical parameters | 680kW / 48U / L2L CDU |
| Rated cooling capacity | 680 kW @ 4.0°C ATD |
| Maximum flow rate – single pump operation | 700L/min, external pressure difference 2.0bar |
| Maximum flow rate – dual pump operation for N+ redundancy | 1050L/min, external pressure difference 3.4bar |
| Secondary coolant type | Pure Water or PG25 |
| Pump redundancy | Single pump (N) / dual pump (N+N) / dual pump switchover |
| Primary pressure drop | 0.8 bar (PG25) under typical conditions (650 L/min) |
| Secondary coolant temperature range | 10–55°C, with dew point control standard |
| Maximum power consumption | 4.5 kW (Single Pump) 7.3 kW (Dual Pump) |
| Dimensions (H × W × D) and weight | 1900 × 600 × 1050 mm, 550 kg |
| Noise level at 3m (10ft) | < 54 dBA |
| Power supply (Europe, Asia and Taiwan) | 3P 380-480 V 50/60 Hz |
| Dual power supply (ATS) | Optional features |
| Primary connections | Top or bottom, 2½-inch sanitary flange |
| Secondary connections | Top or bottom, 2½-inch sanitary flange |
| Secondary filtration | Optional 50um/20um |
| Communication | RS485 RTU modbus, TCP/IP SNMP |
Scroll to view all parameters
Get in Touch
Have a question or want to learn more? Send us a message.