title: "GHV3S 3S Module"
description: "GHV3S integrates BMS (battery management system), PCS(power conversion system), EMS(energy management system) and HV Box (high voltage box) in one module."
---

# GHV3S

Home

Products

GHV3S

![Product image](https://www.gerchamp.com/media/page-assets/uploads/2026/05/8125679e-69b6-4117-8fc2-2d86dd2a957e.webp)

GHV3S

GHV3S integrates BMS (battery management system), PCS(power conversion system), EMS(energy management system) and HV Box (high voltage box) in one module. The self-developed design can realize an intelligent synergy of the product, improve safety performance, save hardware cost, increase conversion efficiency, shorten the development cycle, and reduce the difficulty of operation and maintenance.

Key Features

| Technical Parameter | Value / Details |
| --- | --- |
| Low Cost | All-in-one design shrinks size and cuts total development cost. |
| High Efficiency & Stability | 3S strategic integration ensures fast response and high stability. |
| Flexible Configuration | Flexible configuration adapts to diverse scenarios and ESS products. |
| Convenient O&M | Self-developed system with smart collaboration simplifies O&M. |

Technical Parameters

Product Specifications

Complete technical data for the GHV3S 3S Module.

| Parameter | Result |
|---|---|
| Description | GHV3S-P100U10F / GHV3S-P135U10F |
| Rated power supply | 220Vac / 100~240Vac |
| Power consumption | <200W(without load) |
| Maximum conversion efficiency | 98% |
| Dimension(L*W*H)/weight | 794*800*235mm/<82.55kg / 794*1000*235mm/<100kg |
| Cooling method | Air-cooling |
| Noise level | <75dB |
| Protection level | IP20 |
| Operating temperature/storage temperature /relative humidity | -20~+50℃/-40~+125℃/0~95%(non-condensing) |
| Altitude | <3000m |
| Rated AC power | 100kW / 135kW |
| Wiring | 3-phase 3-wire (on-grid mode),3-phase 3-wire/3-phase 4-wire(off-grid mode) |
| AC overload capaclty | 10%overload |
| Allowable voltage | 380/400Vac(-15%~15%) / 400Vac(-10%~15%) |
| Allowable frequency | 50Hz(-2.5~2.5) / 50Hz(-0.5~0.5) |
| Total harmonic current distortion | ≤5% |
| Power factor | 0.99(-1~1) / (-1~1) |
| Rated DC power | 100kW / 135kW |
| Maximum DC current | 169A / 228A |
| DC access channel | 650~900V / 650~950V |
| / | 2-channel LAN,3-channel CAN(2-channel CAN 2.0,1-channel CAN FD), 4-channel RS485,1-channel RS232,2-channel fiber signal |
| 4-channel DO*L | Voltage range:9~32Vdc |
| Output port | Current:2.2A/single-channel at maximum and 1.1A continuously |
| Single-channel DO*L rated power:26.4W | Single-channel DO*L rated power:26.4W Dual-channel DO*L total rated power:52.8W Four-channel DO*L total rated power:105.6W |
| Single-channel instantaneous power:192W | Single-channel DO*Linstantaneous power:192W Dual-channel DO*Linstantaneous power:384W Four-channel DO*L instantaneous power:768W |
| 4-channel dry contact output | Voltage:24Vdc/1A Electrical isolation:3000Vdc |
| 7-channel DI*Land 2-channel passive Dl | Low voltage range:<0.5VDC |
| Storage /internal memory /port | 8GB/2GB/1-channel USB port(USB2.0) |

Scroll to view all parameters

Architecture

Energy Management System

C&I Energy Management System dashboard — real-time monitoring of site SOC, PCS power, cluster voltage, charge/discharge status, alarm data, and power analytics.

![GHV3S EMS Dashboard](/media/page-assets/uploads/2026/05/8741bc8b-fbb5-4f22-a378-9986aaee414e.webp)

### Related Content

#### Related Products

- [HC-CP135E215F](https://www.gerchamp.com/en-US/products/ci-energy-storage-system) ([Agent MD](https://www.gerchamp.com/en-US/products/ci-energy-storage-system/raw.md)) - All-in-One 135kW/215kWh
- [HC-PP135E215FS](https://www.gerchamp.com/en-US/products/pv-hybrid-backup-ess) ([Agent MD](https://www.gerchamp.com/en-US/products/pv-hybrid-backup-ess/raw.md)) - All-in-One 135kW / 215kWh +2*30kW (MPPT)

#### Related Solutions

- [Commercial & Industrial ESS](https://www.gerchamp.com/en-US/solutions/commercial-and-industrial-ess) ([Agent MD](https://www.gerchamp.com/en-US/solutions/commercial-and-industrial-ess/raw.md)) - Faced with rising energy costs and grid stability challenges, commercial and industrial users.

#### Related Documents & Downloads

- [GHV3S](/media/library/2026/05/0bbc1c0b-05f8-486d-8631-58ba0c7e642f.pdf) - 3S (BMS+PCS+EMS+HV Box) Module


Related Contents

---

**Navigation**

[Home](https://www.gerchamp.com/en-US/) ([MD](https://www.gerchamp.com/en-US/raw.md)) | [Products](https://www.gerchamp.com/en-US/products/) ([MD](https://www.gerchamp.com/en-US/products/raw.md)) | [Solutions](https://www.gerchamp.com/en-US/solutions/) ([MD](https://www.gerchamp.com/en-US/solutions/raw.md)) | [Blog](https://www.gerchamp.com/en-US/blog/) ([MD](https://www.gerchamp.com/en-US/blog/raw.md)) | [About](https://www.gerchamp.com/en-US/about/) ([MD](https://www.gerchamp.com/en-US/about/raw.md)) | [Downloads](https://www.gerchamp.com/en-US/downloads/) ([MD](https://www.gerchamp.com/en-US/downloads/raw.md)) | [Contact](https://www.gerchamp.com/en-US/contact/) ([MD](https://www.gerchamp.com/en-US/contact/raw.md))